| Applications |
Fluke 345 |
Fluke 434 |
Fluke 435 |
Fluke 43B |
Fluke 1735 |
| 1-Phase/3-Phase |
•/- |
•/• |
•/• |
•/- |
•/• |
| Frontline Troubleshooting |
• |
• |
• |
• |
|
| Load study, PQ Survey |
|
• |
• |
|
• |
| Compliance (EN50160) |
|
• |
• |
|
|
| Long-term Analysis |
|
|
• |
|
• |
| Features |
Fluke 345 |
Fluke 434 |
Fluke 435 |
Fluke 43B |
Fluke 1735 |
| Display |
Color Graphical |
Color Graphical |
Color Graphical |
B&W Graphical |
Color Graphical |
| Voltage Channels |
1 |
4 |
4 |
1 |
3 |
| Current Channels |
1 |
4 |
4 |
1 |
4 |
| Included Current Probes |
2000 A |
40A/400A Clamps |
3000A Flexis |
40A/400A Clamps |
15A/150A/3000A Flexis |
| Dust/Water Resistance |
IP40 |
IP51 |
IP51 |
IP51 |
IP65² |
| Safety Rating |
600 V CAT IV |
600 V CAT IV/1000 V CAT III |
600 V CAT IV/1000 V CAT III |
600 V CAT III |
600 V CAT III |
| Software |
Fluke Power Log |
Fluke View |
Fluke Power Log/Fluke View |
Fluke View |
Fluke PowerLog |
| Battery Operation (hours) |
24 |
7 |
7 |
6.5 |
24 |
| Recording Capability |
Fluke 345 |
Fluke 434 |
Fluke 435 |
Fluke 43B |
Fluke 1735 |
| Typical Recording Period (days) |
1 |
7 |
30 |
7 |
30 |
| Memory |
2 MB |
8 MB |
16 MB |
512 KB |
8 MB |
| Min/Max/AVG Logging |
• |
• |
• |
• |
• |
| Flicker |
|
• |
• |
• |
• |
| Harmonics |
• |
• |
• |
• |
• |
| Event Capture |
|
• |
• |
• |
• |
| Waveform Capture |
• |
• |
• |
• |
• |
| User defined Logging |
|
|
• |
|
|
| Sample rate |
9.6 kHz |
20.48 kHz |
20.48 kHz |
12.8 kHz / 15.36 kHz |
10.24 kHz |
| High-speed capture rate |
|
200 kHz |
200 kHz |
25 MHz |
|
| Peak Voltage |
1 kV |
6 kV |
6 kV |
1.25 kV |
|
| Analysis Capability |
Fluke 345 |
Fluke 434 |
Fluke 435 |
Fluke 43B |
Fluke 1735 |
| Statistical Analysis (including EN50160) |
|
• |
• |
|
• |
| Report Generator |
• |
• |
• |
|
• |
| Accuracy |
Fluke 345 |
Fluke 434 |
Fluke 435 |
Fluke 43B |
Fluke 1735 |
| IEC 61000-4-30 Class A Compliant |
|
|
• |
|
|
| Volts RMS |
|
0.5% Vnom |
0.1% Vnom |
±(1%+10 counts) |
±(0.5%+10 counts) |
| Current RMS (excluding clamp unless specified) |
|
±(1%+5 counts) |
±(1%+5 counts) |
±(1%+10 counts) |
±(1%+10 counts) |
| ¹ (8 voltage channels without current) |
| ² (except battery housing) |